Toshiba VF-S9 manual Measures to satisfy the EMC directive, E6580757

Models: VF-S9

1 198
Download 198 pages 1.97 Kb
Page 154
Image 154
9.1.2Measures to satisfy the EMC directive

 

 

 

 

E6580757

 

 

 

 

 

 

 

 

Table 1 EMC standards

 

 

 

 

 

 

 

 

 

Category

Subcategory

General standard

Test standard and level

 

Emission

Radiation noise

EN50081-2

EN 55011, Group 1, Class A

 

 

Transmission noise

EN 55011, Group 1, Class A

 

 

 

 

 

 

 

Static discharge

 

EN 61000-4-2

 

 

 

Radioactive radio-frequency magnetic

 

EN 61000-4-3

 

 

Immunity

contactor field

EN50082-2

 

 

 

First transient burst

EN 61000-4-4

 

 

 

Lightning surge

 

EN 61000-4-5

 

 

 

Radio-frequency induction/transmission

 

EN 61000-4-6

 

 

 

interference

 

 

 

Emission standards other than the above are applied to inverters when used in a commercial environment but not an industrial environment.

Category

Subcategory

General standard

Test standard and level

Emission

Radiation noise

EN50081-2

EN 55011, Group 1, Class B

Transmission noise

EN 55011, Group 1, Class B

 

 

9.1.2Measures to satisfy the EMC directive

This subsection explains what measures must be taken to satisfy the EMC directive.

(1)Insert a recommended EMI filter (Table 2) on the input side of the inverter to reduce radiation and transmis- sion noises. In the combinations listed in Table 2, inverters were checked for conformity with the EMC di- rective. For inverters used in Japan, it is recommended to use the NF series of noise filters.

Table 2 lists noise filters recommended for the inverters.

9

* Dimensions of EMI filter : See 10.4 (Page J-11)

 

 

Table 2 Combinations of inverter and EMI filter

Three-phase 200V class

Combination of inverter and filter

Inverter

Filter for class A

Filter for class B

 

compliance

compliance

VFS9-2002PM

EMF2011BZ

-

VFS9-2004PM

EMF2011BZ

-

VFS9-2007PM

EMF2011BZ

-

VFS9-2015PM

EMF2011BZ

-

VFS9-2022PM

EMF4025DZ

-

VFS9-2037PM

EMF4025DZ

-

VFS9-2055PL

With a built-in filter

EMF4045EZ

VFS9-2075PL

With a built-in filter

EMF4045EZ

VFS9-2110PM *

EMF2080GZ

-

VFS9-2150PM *

EMF2080GZ

-

Three-phase 400V class

Combination of inverter and filter

Inverter

Filter for class A

Filter for class B

 

compliance

compliance

VFS9-4007PL

With a built-in filter

EMF4016CZ

VFS9-4015PL

With a built-in filter

EMF4016CZ

VFS9-4022PL

With a built-in filter

EMF4025DZ

VFS9-4037PL

With a built-in filter

EMF4025DZ

VFS9-4055PL

With a built-in filter

EMF4045EZ

VFS9-4075PL

With a built-in filter

EMF4045EZ

VFS9-4110PL

With a built-in filter

EMF4045FZ

VFS9-4150PL

With a built-in filter

EMF4045FZ

*Wire grounding wire between the EMI filter and EMC plate in order to conform to class A. Wire size : 6mm2 or more (AWG 9 or more)

Wire length : 29cm or less

I-2

Page 154
Image 154
Toshiba VF-S9 manual Measures to satisfy the EMC directive, E6580757