6.15.8 Over-torque trip

: Over-torque trip selection

: Over-torque (trip/alarm) level

: Over-torque (trip/alarm) detection time

: Over-torque (trip/alarm) level hysterisis

Function

 

 

 

 

 

 

 

 

 

 

 

 

 

6

Use the

parameter to trip the inverter if a torque current exceeding the

 

-specified

 

 

level flows for more than the

-specified time. Trip information is displayed as "

".

 

 

 

 

 

(No trip) ...... No tripping (FL relay deactivated).

 

 

 

 

 

 

An overtorque alarm can be put out to the output terminal by setting the output

 

 

 

terminal function selection parameter.

 

 

 

 

 

 

(Trip) .......... The inverter is tripped (FL relay activated) only after a torque current exceeding

 

 

 

the

-specified level has been detected for more than the

 

-

 

 

 

 

specified time.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Title

 

Function

 

Adjustment range

 

Default setting

 

 

 

 

 

 

 

 

 

 

 

 

Over-torque trip selection

 

0: Disabled

 

 

0

 

 

 

 

 

1: Enabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Over-torque (trip/alarm) level

0 250 (%)

 

 

150

 

 

 

 

Over-torque (trip/alarm) detection time

0.00 10.0 (s)

 

 

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

Over-torque (trip alarm) level hysterisis

0 100 (%)

 

 

10

 

 