E6580757
Strip the cable and fix it to the metal
Shielded cableplate by means of a metal saddle for electrical work or equivalent.
9.1.3About the low-voltage directive
The
Applicable standard: EN 50178
Electronic equipment for use in power installations Pollution level: 2 (5.2.15.2)
Overvoltage category: 3
200V class - 3.0mm (5.2.16.1)
400V class - 5.5mm (5.2.16.1)
EN 50178 applies to electrical equipment intended specially for use in power installations, and sets out the condi- tions to be observed for electric shock prevention when designing, testing, manufacturing and installing electronic equipment for use in power installations.
| 9.1.4 | Measures to satisfy the | |
9 | When incorporating the inverter into a machine or system, it is necessary to take the following measures so that | ||
| the inverter satisfies the | ||
| (1) | When installing the inverter outside the cabinet, provide a protective means for the inverter's wiring hole to | |
|
| prevent workers from putting their fingers through the hole and touching an | |
|
| inverter. | |
| (2) | Do not connect two or more wires to the main circuit earth terminal of the inverter. If necessary, install an | |
|
| additional earth terminal on the metal plate on which the inverter is installed and connect another cable to it. | |
|
| Or install the EMC plate (attached as standard) and another cable connect to earth terminal on the EMC | |
|
| plate. Refer to the table 10.1 for earth cable sizes. | |
| (3) | Install a |