FRU Removal and Replacement
9.Inspect the power supply to ensure that the green LED is illuminated. If the green LED is extinguished, go to "MAP 0000: Start MAP" on page
10.At the HAFM server’s Hardware View, select the Event Log option from the Logs icon. The Event Log displays. Ensure the following event codes appear in the log:
—203 - Power supply AC voltage recovery.
—204 - Power supply DC voltage recovery.
11.At the HAFM server’s Hardware View, observe the power supply graphic and ensure no alert symbols appear that indicate a failure (yellow triangle or red diamond). If a problem is indicated, go to "MAP 0000: Start MAP" on page
12.Perform the data collection procedure (refer to "Collecting Maintenance Data" on page
13.Clear the switch system error (ERR) LED:
a.At the HAFM server’s Hardware View,
b.Click the Clear System Error Light menu selection.
RRP: Cooling Fan
Use the following procedures to remove or replace a cooling fan from the rear of the switch. No tools are required.
Removal
To remove a cooling fan:
1.Identify the defective cooling fan from the illuminated amber LED on the fan or failure information at the HAFM server’s Hardware View.
2.Loosen the fan retaining screw in the upper right corner of the fan. This is a captive screw that will remain in the fan assembly.
3.Grasp the fan handle and pull the fan FRU out of the chassis.