MERLIN LEGEND Communications System Release 6.1

Issue 1

Installation 555-661-140

August 1998

Installing the Control Unit

Page 2-7

AC Power and Grounding

 

 

If the printer or PC is 50 ft. (15 m) or more from the control unit, or is plugged into a different AC circuit, Asynchronous Data Units (ADUs) must be installed as well. Chapter 5, “Installing the PC, CAT, or Printer,” includes complete installation instructions.

The AC power requirements indicated in “AC Outlet Tests,” on page 2-8, must be met.

From AC

 

Load Center

 

(2 separately

 

fused 15 A

Ground Wire

circuits)

#14 AWG

 

4" Box (RACO 230

HUBBELL

or equivalent)

 

Receptacles

 

(5262 15 A

 

or equivalent)

 

Single-Point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4" Cover

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(RACO 807

Ground

 

 

 

 

 

 

 

 

 

Ground Bar Mounted

 

 

 

 

 

 

 

 

 

or equivalent)

 

 

 

 

 

 

 

 

 

Ground Wire

on a 4" Box (Square

 

 

 

 

 

 

 

 

 

"D" PK9GTA or

 

 

 

 

 

 

 

 

 

#6 AWG Copper

 

 

 

 

 

 

 

approved equivalent)

 

 

 

Approved

 

 

 

 

 

 

 

 

 

Building Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

#12 or #14 AWG Copper Wire to Each Power Supply Grounding Screw

Figure 2-1. AC Grounding Requirements

! CAUTION:

The AC outlet for the control unit cannot be switch-controlled. Plugging the control unit into such an

Page 72