MERLIN LEGEND Communications System Release 6.1

Issue 1

Installation 555-661-140

August 1998

Installing the Control Unit

Page 2-26

Installing the Auxiliary Power Unit

 

 

Installing the Auxiliary Power Unit

The Control Unit Diagram on the back of Form 1, System Planning, indicates whether an auxiliary power unit is required for the carrier that you are installing.

NOTE:

Use the 9024 auxiliary power unit for new installations. You can continue to use a previously installed 335A auxiliary power unit, as long as no new telephones or modules are added to the carrier.

To install an auxiliary power unit, follow the steps below. Refer to Figure 2–8 throughout this procedure.

! Turn off the switch on the power supply.

! Mount the auxiliary power unit on a surface (preferably the backboard) within 2 ft. (61 cm) of the control unit.

! Plug the power unit line cord into the AUX POWER INPUT jack on the power supply.

! Plug the other end of the line cord into the AUX POWER jack on the auxiliary power unit.

! CAUTION:

Do not plug the power supply or the auxiliary power unit into the AC outlet until you are ready to turn on the system, as described in “Powering Up the System” later in this chapter.

If the system is backed up by an Uninterruptible Power Supply (UPS), connect the auxiliary power to the UPS.

Do not attach the power cord(s) to any building surfaces.

Use only the power unit line cord supplied with the auxiliary power unit. An incorrect cord will damage the power supply and may damage modules.

Page 91
Image 91
Lucent Technologies 555-661-140 manual Installing the Auxiliary Power Unit