MERLIN LEGEND Communications System Release 6.1

Issue 1

Installation 555-661-140

August 1998

Installing the Control Unit

Page 2-6

AC Power and Grounding

 

 

AC Power and Grounding

Proper power and grounding are essential for the system to run correctly and safely.

! CAUTION:

If any of the following requirements are not met, the customer must contact a licensed electrician. Do not install the system until all requirements are met.

Verify that all of the following power and grounding requirements are met:

The load center of appropriate current rating must be equipped with circuit breaker(s) labeled 120 V AC, 15 amps.

Each breaker must protect one dedicated quad AC outlet or two dedicated duplex AC outlets.

All AC outlets must connect to the same load center and the ground wire must connect to the single-point ground bar on the first AC outlet (see Figure 2–1).

One outlet must have an attached ground bar connected by a #6 AWG copper wire to an approved ground (see “Approved Grounds,” later in this chapter, for a description of approved grounds). This ground bar is the system’s single-point ground (see Figure 2–1).

To prevent someone from accidentally shutting off the power, do not connect the control unit to a switch-controlled outlet.

The AC outlet should be within 5 ft. (152 cm) of the control unit.

Each carrier requires one AC outlet receptacle.

Auxiliary equipment requires additional AC outlets.

If a printer or PC is installed on the system, it must be plugged into the same AC branch as the power supply of the basic carrier.