MERLIN LEGEND Communications System Release 6.1

Issue 1

Installation 555-661-140

August 1998

Installing the Control Unit

Page 2-8

AC Power and Grounding

 

 

outlet invites accidental disconnection of the system. The AC outlet must be properly wired as described in “AC Outlet Tests.”

Table 2-2. AC Power Requirements

Parameter

Value

 

Nominal voltage

117 V AC

Voltage range

110–125 V AC

Frequency

60 Hz +/– 5%

Maximum current

3 amps per power supply

Power consumption

225 watts per power supply

 

 

 

AC Outlet Tests

If the AC outlet tests indicate that any of the power requirements in Table 2–2 are not met, your customer must contact a licensed electrician. Do not install the system until all requirements are met.

If the AC outlet tests reveal any of the following conditions, they must be corrected before you install the system:

Open ground

Hot and neutral reversed

Open hot

Open neutral

Hot and ground reversed