Lucent Technologies 555-661-140 manual Environment, Ventilation

Models: 555-661-140

1 355
Download 355 pages 10 Kb
Page 67
Image 67

MERLIN LEGEND Communications System Release 6.1

Issue 1

Installation 555-661-140

August 1998

Installing the Control Unit

Page 2-2

Overview

 

 

The following sections provide detailed instructions for these installation procedures. Follow the procedures in the order in which they are presented.

Environment

The control unit must be installed on a backboard. The placement of the backboard, and the control unit on it, requires careful consideration. Make sure you install the backboard in an area that meets all of the environmental requirements listed in Table 2–1.

Table 2-1. Environmental Requirements

Operating

40o104oF (4o40oC)

Temperatures

Optimal temperature: 60oF (15.6oC)

Humidity

20%–80%

 

 

Airborne

Do not expose the control unit to moisture, corrosive gases,

Contamination

dust, chemicals, spray paint, or similar material.

 

 

Ventilation

Allow at least 1 in. (2.54 cm) on the right and left sides of the

 

control unit and at least 12 in. (30.48 cm) above and below it

 

to prevent overheating.

 

Do not place the control unit near extreme heat sources (for

 

example: furnaces, heaters, attics, or direct sunlight).

 

 

Electrical Fields

Do not expose the control unit to devices that generate

 

electrical currents causing interference (such as arc welders

 

or motors).

 

 

Heat

Basic carrier: 500 Btu/hr

Dissipation

Basic carrier: with one expansion carrier 1000 Btu/hr

 

Basic carrier: with two expansion carriers 1500 Btu/hr

 

 

Page 67
Image 67
Lucent Technologies 555-661-140 manual Environment, Ventilation