MERLIN LEGEND Communications System Release 6.1

Issue 1

Installation 555-661-140

August 1998

Installing the Control Unit

Page 2-11

AC Power and Grounding

 

 

Because equipment can be located throughout a building, the National Electrical Code requires that the ground point for the central office trunk protector be bonded to the AC power ground as shown in Figure 2–3.

The AC outlet and the single-point ground bar must be properly grounded as shown in Figure 2–1 and Figure 2–3.

Each power supply in the control unit must be connected to the single-point ground bar by a #12 AWG or a #14 AWG solid copper wire. Figures 2–1 and 2–3 show this connection.

This wire run should be as short as possible, preferably within 5 ft. (152 cm), not to exceed 10 ft. (305 cm). See “Approved Grounds,” later in this chapter, for more information.

The AC outlet must be connected to the 147A protector with a #12 AWG or a #14 AWG solid copper wire.