!WARNING
Anchor The Equipment Rack. The equipment rack must be anchored to an unmovable support to prevent it from falling over when one or more servers are extended in front of it on slide assemblies. The anchors must be able to withstand a force of up to 113 kg (250 lbs). You must also consider the weight of any other device installed in the rack.
Avoid Injury. The minimum server configuration weighs 38 kg (85 lbs); the maximum configuration weighs 45 kg (100 lbs). To avoid personal injury when installing the server, have someone help you position the server in the rack.
Do not attempt to lift or move the server unit by the handles on the power supplies.
1.Pull the telescoping center bar (2 on the following figure) out of each slider assembly on the rack until it locks in place.
2.With someone helping you, use the handles on the sides of the rack unit to lift and slide the unit into the slider assemblies.
Align the small bars (1) attached to the sides of the system unit with the extended center bars (2).
TCarefully slide the server unit into the extended center bars until it stops.
Press in on the safety latches (4) on the small bars and carefully slide the server unit all the way into the rack.
3.Check that the server unit slides in and out of the rack. Grasp the two handles on the sides of the unit and slowly pull the unit out and push it back in.
4.Connect all external peripherals and cables.
5.Connect the two power supply cables to the back of the server unit and to a power source.
6.Power on the server unit.