FM-3 Programming Module Reference Manual

No Prog

This fault will be displayed on initial power-up indicating that no configuration has been downloaded to the FM-3 module. To clear the fault, download a valid configuration to the FM-3 module.

Cn Tmout

A connection time-out occurs when a FM-3DN or any other device on the network does not receive a packet of information that it was expecting. Connection time-out faults are self- resetting unless ten are received in a row causing a buss-off condition.

BusOff

This fault occurs when the FM-3DN experiences ten connection time-outs in a row. This situation forces a buss-off fault that is resetable only by cycling logic power on the FM-3DN. Buss-offs are generally caused by either DeviceNet wiring issues, or devices with different baud rate settings residing on the same network.

DupMacID

This fault occurs when the FM-3DN's MacID is the same as another MacID on the network. Logic power must be cycled or an appended program downloaded via PowerTools Pro to the FM-3DN.

Analog Outputs

The drive has two 10 bit Analog Outputs which may be used for diagnostics, monitoring or control purposes. These outputs are referred to as Channel 1 and Channel 2. They can be accessed from the command connector on the drive or from the diagnostics output pins located on the front of the drive.

Default Analog Output Source:

Channel 1 = Velocity Feedback

Channel 2 = Torque Command

Output

Source

Offset

Scale

 

 

 

 

1

Velocity Feedback

0

600 RPM/volt

 

 

 

 

2

Torque Command

0

30% /volt

 

 

 

 

Analog Output Offset units:

Velocity Feedback = RPM