Tuning Procedure

Once the initial setup has been completed, you can run the system to determine if the level of tuning is adequate for the application. There are basically four levels of tuning for a drive.

No Tuning

Basic Level

Intermediate Level

Fully Optimized Level

Each level is slightly more involved than the previous one requiring you to enter more information. If your system needs optimization, we recommend that you start with the Basic Level, then determine if further tuning is needed based on axis performance.

The setup procedures explained here assume that you are using PowerTools FM-3 software or an FM-P.

Initial settings

Set the drive tuning parameters as follows:

Inertia Ratio = 0

Friction = 0

Response = 50

High Performance Gains = Enabled

Feedforwards = Disabled

Tuning steps

If your Inertia Ratio is greater than 10 times the motor inertia go directly to the Intermediate Level tuning.

No Tuning

No tuning will be required in most applications where the load inertia is 10 times the motor inertia or less.

Basic Level

Adjust Response to obtain the best performance.

Intermediate Level

1.Calculate or estimate the load inertia. It is always better to estimate low.

2.Disable the drive.

214