11.20Checking sensor circuitry

Troubleshooting

11.20Checking sensor circuitry

Problems with sensor circuitry can cause several alarms, including sensor failure and a variety of out-of-range conditions. Testing involves:

Inspecting the cable that connects the transmitter to the sensor

Measuring the resistances of the sensor's pin pairs and RTDs

Ensuring that the circuits are not shorted to each other or to the sensor case

Note: To check the sensor circuitry, you must remove the transmitter from the sensor. Before performing this test, ensure that all other applicable diagnostics have been performed. Diagnostic capabilities of the Model 2400S transmitter have been greatly enhanced, and may provide more useful information than these tests.

1.Follow appropriate procedures to ensure that the process of checking the sensor circuitry does not interfere with existing measurement and control loops.

2.Disconnect the DeviceNet cable from the DeviceNet connector on the Model 2400S DN transmitter.

3.If the transmitter is in a hazardous environment, wait five minutes.

4.Check the sensor cable and sensor connection:

a.Referring to Figure 11-2,loosen the four captive transmitter housing cover screws and remove the transmitter housing cover.

b.Loosen the two captive user interface screws.

c.Gently lift the user interface module, disengaging it from the connector on the transmitter.

d.Two captive screws (2.5 mm hex head) hold the transmitter in the housing. Loosen the screws and gently lift the transmitter away from the housing. Allow the transmitter to hang by the cable.

e.Check the cable for any signs of damage.

f.Ensure that the cable is fully plugged in and making a good connection. If it is not, reseat the cable, reassemble the transmitter and sensor, and check operation.

Compensation

Measurement Performance

Troubleshooting

Defaults

Configuration and Use Manual

125