Emerson Process Management 2400S 8.10.6IrDA port usage, 8.10.7Digital communications fault action

Models: 2400S

1 188
Download 188 pages 39.36 Kb
Page 81
Image 81
8.10.6IrDA port usage

Optional Configuration

The primary reason to disable Modbus ASCII support is to allow a wider range of Modbus addresses for the service port.

To enable or disable Modbus ASCII support:

Using ProLink II, see Figure B-2.

Using the display menus, see Figure B-6.

8.10.6IrDA port usage

The IrDA port on the display can be enabled or disabled. If enabled, it can be set for read-only or read/write access.

To enable or disable the IrDA port:

Using ProLink II, see Figure B-2.

Using the display menus, see Figure B-6.

Using a DeviceNet tool, see Table C-9.

To configure the IrDA port for read-only or read-write access:

Using ProLink II, see Figure B-2.

Using the display menus, see Figure B-6.

Using a DeviceNet tool, see Table C-9.

8.10.7Digital communications fault action

Digital communications fault action controls how digital communications will be affected by fault conditions. Table 8-12lists the options for digital communications fault action.

Note: Digital communications fault action does not affect the alarm status bits. For example, if digital communications fault action is set to None, the alarm status bits will still be set if an alarm occurs. See Section 7.6 for more information.

Table 8-12Digital communications fault action options

 

Option

 

 

 

 

 

 

ProLink II label

DeviceNet label

DeviceNet code

Definition

 

 

 

 

Upscale

Upscale

0

Process variables indicate the value is greater than

 

 

 

the upper sensor limit. Totalizers stop counting.

 

 

 

 

Downscale

Downscale

1

Process variables indicate the value is less than the

 

 

 

lower sensor limit. Totalizers stop counting.

 

 

 

 

Zero

Zero

2

Flow rates go to the value that represents zero flow.

 

 

 

Density and temperature go to zero. Totalizers stop

 

 

 

counting.

 

 

 

 

Not-A-Number

NAN

3

Process variables report IEEE NAN. Totalizers stop

(NAN)

 

 

counting.

 

 

 

 

Flow to Zero

Flow goes to zero

4

Flow rates go to the value that represents zero flow;

 

 

 

other process variables are not affected. Totalizers

 

 

 

stop counting.

 

 

 

 

None (default)

None

5

Process variables reported as measured.

 

 

 

 

Using a DeviceNet Tool

Required Configuration

Using the Transmitter

Optional Configuration

Configuration and Use Manual

73

Page 81
Image 81
Emerson Process Management 2400S manual 8.10.6IrDA port usage, 8.10.7Digital communications fault action