Emerson Process Management 2400S manual Gas Standard Volume Object

Models: 2400S

1 188
Download 188 pages 39.36 Kb
Page 154
Image 154
Gas Standard Volume Object (0x64)

Device Profile

Table C-3Analog Input Point Object (0x0A) – Instance 3 (density) continued

Attrib

 

 

 

 

 

 

ID

Name

Data type

Service

Mem

Description

Comments

 

 

 

 

 

 

 

104

Damping

REAL

Set

NV

Density damping value

Unit = seconds

 

 

 

 

 

 

 

105

Cutoff

REAL

Set

NV

Value below which density

 

 

 

 

 

 

will be reported as 0

 

 

 

 

 

 

 

 

106

Meter factor

REAL

Set

NV

A multiplier to the

 

 

 

 

 

 

calculated density

 

 

 

 

 

 

 

 

Table C-4Analog Input Point Object (0x0A) – Instance 4 (temperature)

Attrib

 

 

 

 

 

 

ID

Name

Data type

Service

Mem

Description

Comments

 

 

 

 

 

 

 

3

Value

REAL

Get

V

Current value of

Based on Attribute 8

 

 

 

 

 

temperature process

 

 

 

 

 

 

variable

 

 

 

 

 

 

 

 

4

Status

BOOL

Get

V

Point status

• 0 = Good

 

 

 

 

 

 

• 1 = Alarm state

 

 

 

 

 

 

 

8

Value data type

USINT

Get

V

Data type used to report

• 1 = REAL

 

 

 

 

 

mass flow process

 

 

 

 

 

 

variable

 

 

 

 

 

 

 

 

102

Value

UINT

Set

NV

Temperature

See Table 6-6for unit

 

engineering

 

 

 

measurement unit

codes.

 

units

 

 

 

 

 

 

 

 

 

 

 

 

104

Damping

REAL

Set

NV

Temperature damping

Unit = seconds

 

 

 

 

 

value

 

 

 

 

 

 

 

 

C.3

Gas Standard Volume Object (0x64)

 

 

 

Table C-5Gas Standard Volume Object (0x64) – Instance 1

 

 

Attrib

 

 

 

 

 

 

ID

Name

Data type

Service

Mem

Description

Comments

 

 

 

 

 

 

 

1

Gas standard

REAL

Get

V

Current value of gas

 

 

volume flow

 

 

 

standard volume flow

 

 

 

 

 

 

process variable

 

 

 

 

 

 

 

 

2

Gas standard

REAL

Get

V

Current value of gas

 

 

volume total

 

Reset(1)

 

standard volume total

 

 

 

 

 

 

 

 

3

Gas standard

REAL

Get

V

Current value of gas

 

 

volume

 

Reset(2)

 

standard volume

 

 

inventory

 

 

 

inventory

 

 

 

 

 

 

 

 

4

Reference

REAL

Set

NV

Reference density of gas

 

 

density

 

 

 

being measured

 

 

 

 

 

 

 

 

5

Gas standard

UINT

Set

NV

Gas standard volume flow

See Table 6-4for unit

 

volume flow

 

 

 

measurement unit

codes.

 

units

 

 

 

 

 

 

 

 

 

 

 

 

6

Gas standard

UINT

Get

V

Gas standard volume total

Transmitter

 

volume total and

 

 

 

and inventory units

automatically

 

inventory units

 

 

 

 

determines this based

 

 

 

 

 

 

on Attribute 102.

See Table C-14for unit codes.

146

Micro Motion® Model 2400S Transmitters for DeviceNet

Page 154
Image 154
Emerson Process Management 2400S manual Gas Standard Volume Object