Required Transmitter Configuration

6.3Configuring the measurement units

For each process variable, the transmitter must be configured to use the measurement unit appropriate to your application.

To configure measurement units for process variables, see the menu flowcharts in Figure 6-3.For details on measurement units for each process variable, see Sections 6.3.1 through 6.3.4.

The measurement units used for totalizers and inventories are assigned automatically, based on the measurement unit configured for the corresponding process variable. For example, if kg/hr (kilograms per hour) is configured for mass flow, the unit used for the mass flow totalizer and mass flow inventory is kg (kilograms). DeviceNet codes used for the measurement units are listed in Tables C-12through C-14.

Note: Pressure unit configuration is required only if you are using pressure compensation (see Section 9.2) or you are using the Gas Wizard and you need to change the pressure units (see Section 8.2).