Using the Transmitter
In addition, the transmitter maintains alarm history for the 50 most recent alarm occurrences. Alarm history includes:
•The alarm code
•The “alarm active” timestamp
•The “alarm inactive” timestamp
•The “alarm acknowledged” timestamp
When the transmitter detects an alarm condition, it checks the severity level of the specific alarm and performs the actions described in Table
Table 7-6 Transmitter responses to status alarms
|
| Transmitter response |
|
Alarm severity |
|
|
|
|
| Digital communications | |
level(1) | Status flags | Alarm history | fault action |
|
|
|
|
Fault | • “Alarm active” status flag set | “Alarm active” record | Activated after configured fault |
| immediately | written to alarm history | timeout has expired (if |
| • “Alarm unacknowledged” status | immediately | applicable)(2) |
| flag set immediately |
|
|
|
|
|
|
Informational | • “Alarm active” status flag set | “Alarm active” record | Not activated |
| immediately | written to alarm history |
|
| • “Alarm unacknowledged” status | immediately |
|
| flag set immediately |
|
|
|
|
|
|
Ignore | • “Alarm active” status flag set | No action | Not activated |
| immediately |
|
|
•“Alarm unacknowledged” status flag set immediately
(1)See Section 8.8 for information on setting the alarm severity level.
(2)See Sections 8.10.7 and 8.10.8 for more information on digital communications fault action and fault timeout.
When the transmitter detects that the alarm condition has cleared:
•The first status flag is set to “inactive.”
•Digital communications fault action is deactivated (Fault alarms only).
•The “alarm inactive” record is written to alarm history (Fault and Informational alarms only).
•The second status flag is not changed.
Operator action is required to return the second status flag to “acknowledged.” Alarm acknowledgment is not necessary. If the alarm is acknowledged, the “alarm acknowledged” record is written to alarm history.
7.6.1Using the display
The display shows information only about active Fault or Informational alarms, based on alarm status bits. Ignore alarms are filtered out, and you cannot access alarm history via the display.
To view or acknowledge alarms using the display menus, see the flowchart in Figure
If the transmitter does not have a display, or if operator access to the alarm menu is disabled (see Section 8.9.3), alarms can be viewed and acknowledged using ProLink II or a DeviceNet tool. Alarm acknowledgment is not required.
Additionally, the display may be configured to enable or disable the Ack All function. If disabled, the Ack All screen is not displayed and alarms must be acknowledged individually.
44 | Micro Motion® Model 2400S Transmitters for DeviceNet™ |