Optional Configuration

Table 8-9Display functions

Parameter

Enabled (shown)

Disabled (hidden)

 

 

 

Totalizer start/stop

Operators can start or stop totalizers using the

Operators cannot start or stop totalizers using

 

display.

the display.

 

 

 

Totalizer reset

Operators can reset the mass and volume

Operators cannot reset the mass and volume

 

totalizers using the display.

totalizers using the display.

 

 

 

Auto scroll(1)

The display automatically scrolls through each

Operators must Scroll to view process

 

process variable at a configurable rate.

variables.

 

 

 

Off-line menu

Operators can access the off-line menu (zero,

Operators cannot access the off-line menu.

 

simulation, and configuration).

 

 

 

 

Off-line password(2)

Operators must use a password to access the

Operators can access the off-line menu

 

off-line menu.

without a password.

 

 

 

Alarm menu

Operators can access the alarm menu

Operators cannot access the alarm menu.

 

(viewing and acknowledging alarms).

 

 

 

 

Acknowledge all

Operators are able to acknowledge all current

Operators must acknowledge alarms

alarms

alarms at once.

individually.

 

 

 

(1)If enabled, you may want to configure Scroll Rate.

(2)If enabled, the off-line password must also be configured.

To configure these parameters:

Using ProLink II, see Figure B-3.

Using the display menus, see Figure B-6.

Using a DeviceNet tool, see Table C-9.Note the following:

If you use the display to disable access to the off-line menu, the off-line menu will disappear as soon as you exit the menu system. If you want to re-enable access, you must use ProLink II or a DeviceNet tool.

Scroll Rate is used to control the speed of scrolling when Auto Scroll is enabled. Scroll Rate defines how long each display variable (see Section 8.9.5) will be shown on the display. The time period is defined in seconds; e.g., if Scroll Rate is set to 10, each display variable will be shown on the display for 10 seconds.

The off-line password prevents unauthorized users from gaining access to the off-line menu. The password can contain up to four numbers.

If you are using the display to configure the display:

-You must enable Auto Scroll before you can configure Scroll Rate.

-You must enable the off-line password before you can configure the password.

8.9.4Configuring the LCD backlight

The backlight of the LCD panel on the display can be turned on or off. To turn the backlight on or off,

Using ProLink II, see Figure B-3.

Using the display menus, see Figure B-6.

Using a DeviceNet tool, see Table C-9.

68

Micro Motion® Model 2400S Transmitters for DeviceNet

Page 76
Image 76
Emerson Process Management 2400S manual 9Display functions, Configuring the LCD backlight