Image 71
Table 8-6Event actions continued

Optional Configuration

Table 8-6Event actions continued

 

 

DeviceNet

 

ProLink II label

Display label

code

Description

 

 

 

 

Reset all totals

RESET ALL

8

Resets the value of all totalizers to 0

 

 

 

 

Start/stop all totalization

START STOP

9

If totalizers are running, stops all totalizers

 

 

 

If totalizers are not running, starts all totalizers

 

 

 

 

Increment current ED

INCR CURVE

18

Changes the active enhanced density curve from 1 to

curve

 

 

2, from 2 to 3, etc.(4)

 

 

 

 

(1)Displayed only if Volume Flow Type = Liquid.

(2)Displayed only if Volume Flow Type = Gas.

(3)Available only if the petroleum measurement application is installed.

(4)Available only if the enhanced density application is installed.

Example

Define Event 1 to be active when the mass flow rate in forward or

 

backward direction is less than 2 lb/min. Additionally, if this occurs, all

 

totalizers should be stopped.

Using ProLink II:

1.Specify lb/min as the mass flow unit. See Section 6.3.1.

2.Configure the Flow Direction parameter for bidirectional flow. See Section 8.5.

3.Select Event 1.

4.Configure:

Event Type = Low

Process Variable (PV) = Mass Flow Rate

Low Setpoint (A) = 2

5.In the Discrete Input panel, open the dropdown list for Start/Stop All Totalization and select Discrete Event 1.

Using a DeviceNet tool:

1.Specify lb/min as the mass flow unit. See Section 6.3.1.

2.Configure the Flow Direction parameter for bidirectional flow. See Section 8.5.

3.In the Diagnostics Object (0x66), Instance 1, set the following attributes:

Discrete event index (Attribute 6) = 0

Discrete event action (Attribute 7) = 1

Discrete event process variable (Attribute 10) = 0

Discrete event setpoint A (Attribute 8) = 2

Discrete event action code (Attribute 84) = 9

Discrete event assignment (Attribute 85) = 57

Using a DeviceNet Tool

Required Configuration

Using the Transmitter

Optional Configuration

Configuration and Use Manual

63