Optional Configuration
If the transmitter detects slug flow:
•A slug flow alarm is posted immediately.
•During the slug duration period, the transmitter holds the mass flow rate at the last measured
•If slugs are still present after the slug duration period expires, the transmitter forces the mass flow rate to 0, independent of the mass flow rate measured by the sensor. Mass flow rate is reported as 0 and all internal calculations that include mass flow rate will use 0.
•When process density returns to a value within the slug flow limits, the slug flow alarm is cleared and the mass flow rate reverts to the actual measured value.
To configure slug flow parameters:
•Using ProLink II, use the Density panel in the Configuration window. See Figure
•Using a DeviceNet tool, set Attributes 3, 4, and 5 in the Diagnostics Object (0x66), Instance 1. See Table
Note: This functionality is not available via the display menus.
Note: The slug flow limits must be entered in g/cm3, even if another unit has been configured for density. Slug flow duration is entered in seconds.
Note: Raising the low slug flow limit or lowering the high slug flow limit will increase the possibility of slug flow conditions. Conversely, lowering the low slug flow limit or raising the high slug flow limit will decrease the possibility of slug flow conditions.
Note: If slug flow duration is set to 0, the mass flow rate will be forced to 0 as soon as slug flow is detected.
8.8Configuring status alarm severity
The Model 2400S transmitter can report faults in the following ways:
•Setting the “alarm active” status bit
•Writing an “alarm active” record to alarm history
•Implementing the digital communications fault action (see Section 8.10.7)
Status alarm severity determines which methods the transmitter will use when a specific alarm condition occurs, as described in Table
Table | Alarm severity levels and fault reporting |
| ||
|
|
| Transmitter action if condition occurs | |
|
|
|
|
|
|
| “Alarm active” | “Alarm active” record | Digital communications |
Severity level | status bit set? | written to history? | fault action activated? (1) | |
|
|
|
|
|
Fault |
| Yes | Yes | Yes |
|
|
|
|
|
Informational |
| Yes | Yes | No |
|
|
|
|
|
Ignore |
| Yes | No | No |
|
|
|
|
|
(1)For some alarms, the digital communications fault action will not begin until the fault timeout has expired. To configure fault timeout, see Section 8.10.8. Other fault reporting methods occur as soon as the fault condition is recognized. Table
Using a DeviceNet Tool
Required Configuration
Using the Transmitter
Optional Configuration
Configuration and Use Manual | 65 |