Detailed Command Descriptions

ALARM Displays the current alarm conditions by severity level. For each level, the specific events that caused an alarm are listed, along with a brief description of each alarm. Alarm levels are:

ALL—All alarm classes

INFORM—Non-persistent information

MINOR—Minor alarm

MAJOR—Major alarm

CRITICAL—Critical alarm

Optional argument:

HEX= —Displays the hex bit codes for the current alarm condition by class. For each specific event that causes an alarm, the corresponding bit is set. Event numbers are matched to the appropriate hex code by a relationship of 2n.

APLIST Configures a list of approved APs.

Optional arguments:

APx=<integer> Configures a list of approved APs. X is a number from 1–50, and integer is the serial number of an approved AP (1–99999999). To delete an entry, enter a serial number of 0; this indicates that the slot is not filled.

AP1=<integer>Serial Number of approved AP AP2=<integer>Serial Number of approved AP . -to-

AP50=<integer>Serial Number of approved AP

CLEAR—Clears all entries in the AP list. Be sure to set RESTRICT to OFF before using this command to avoid restricting Remotes to associating with an empty list.

CMD—Displays all settable optional arguments and their current values. You can copy this list to a text file as a record of your configuration.

RESTRICT=<ONOFF>—Turns on or off restricting registration to APs in the list.

ON—The Remote can only associate with an AP on the list.

OFF—The Remote can associate with any AP.

GFK-2489 Chapter 4 Remote Radio Management 4-5