Command Set

5013 RTD Input

 

 

$aaSiArrff

$aaSiArrff

address of an ADAM-5000 system.

(cr) is the terminating character, carriage return (0Dh).

Example command: $35S3A2000(cr)

response: !35(cr)

The RTD input module in slot 3 of the ADAM-5000 system at address 35h is configured to an RTD type Pt -100 to 100° C, engineering unit data format, and integration time 50ms (60Hz). The response indicates that the command has been received.

6-22

ADAM-5000

Page 144
Image 144
Advantech RS-485 user manual Example command $35S3A2000cr