5013/5017/5017H/5018

Command Set

Analog Input Alarm

 

 

$aaSiCjRhU

$aaSiCjRhU

Name

Read Alarm Limit

Description

Returns the High/Low alarm limit value for the specified

 

input channel in the addressed ADAM-5000 system

Syntax

$aaSiCjRhU(cr)

 

$ is a delimiter character.

 

aa (range 00-FF) represents the 2-character hexadecimal

 

address of an ADAM-5000 system.

 

SiCj identifies the desired slot i (i : 0 to 3) and the

 

desired analog input channel j (j : 0 to 7).

 

RhU is the Read Alarm Limit command.

 

h indicates alarm type and can have the value H = High

 

alarm, L = Low alarm

 

(cr) represents terminating character, carriage return

 

(0Dh)

Response

!aa(data)(cr) if the command was valid

 

There is no response if the system detects a syntax error

 

or communication error or if the specified address does

 

not exist.

 

! delimiter character indicating a valid command was

 

received.

 

aa represents the 2-character hexadecimal address of the

 

corresponding ADAM-5000 system.

 

(data) represents the desired alarm limit setting. The

 

format is always in engineering units.

 

(cr) represents terminating character, carriage return

 

(0Dh)

6-86

ADAM-5000

Page 208
Image 208
Advantech RS-485 user manual Syntax $aaSiCjRhUcr