5013/5017/5017H/5018

Command Set

Analog Input Alarm

 

 

$aaSiCjAh

$aaSiCjAh

Name

Read Alarm Mode

Description

Returns the alarm mode for the specified channel in the

 

specified ADAM-5000 system.

Syntax

$aaSiCjAh(cr)

 

$ is a delimiter character.

 

aa (range 00-FF) represents the 2-character hexadecimal

 

address of an ADAM-5000 system.

 

SiCj identifies the desired slot i (i : 0 to 3) and the

 

desired channel j (j : 0 to 7).

 

Ah is the Read Alarm Mode command.

 

h indicates alarm type and can have the value H = High

 

alarm, L = Low alarm

 

(cr) represents terminating character, carriage return

 

(0Dh)

Response

!aas(cr) if the command was valid

 

There is no response if the system detects a syntax error

 

or communication error or if the specified address does

 

not exist.

 

! delimiter character indicating a valid command was

 

received.

 

aa represents the 2-character hexadecimal address of the

 

corresponding ADAM-5000 system.

 

s indicates alarm mode and can have the value M =

 

Momentary mode, L = Latching mode

 

(cr) represents terminating character, carriage return

 

(0Dh)

6-74

ADAM-5000

Page 196
Image 196