5013/5017/5017H/5018

Command Set

Analog Input Alarm

 

 

$aaSiCjRhC

$aaSiCjRhC

Name

Read Alarm Connection

Description

Returns the High/Low alarm limit output connection of a

 

specified input channel in the addressed ADAM-5000

 

system

Syntax

$aaSiCjRhC(cr)

 

$ is a delimiter character.

 

aa (range 00-FF) represents the 2-character hexadecimal

 

address of an ADAM-5000 system.

 

SiCj identifies the desired slot i (i : 0 to 3) and the

 

desired analog input channel j (j : 0 to 7).

 

RhC is the Read Alarm Connection command.

 

h indicates alarm type and can have the value H = High

 

alarm, L = Low alarm

 

(cr) represents terminating character, carriage return

 

(0Dh)

Response

!aaSkCn(cr) if the command was valid

 

There is no response if the system detects a syntax error

 

or communication error or if the specified address does

 

not exist.

 

! delimiter character indicating a valid command was

 

received.

 

aa represents the 2-character hexadecimal address of the

 

corresponding ADAM-5000 system.

 

SkCn identifies the desired slot k (k : 0 to 3) and the

 

desired digital output point n (n : 0 to F) to which the

 

input alarm is connected. If the values of k and n are ‘*’,

 

the analog input has no connection with a digital output

 

point.

6-82

ADAM-5000

Page 204
Image 204
Advantech RS-485 user manual Syntax $aaSiCjRhCcr