Command Set | 5017H Analog Input |
|
|
#aaSi | #aaSi |
the interrogated module of the specified system. The
(dddd)from all channels is shown in sequence from 7 to 0. If (dddd)=” “, it means the channel is invalid.
(cr) is the terminating character, carriage return (0Dh).
Example command: #35S3(cr)
response: +6.000 +7.000 +8.125 +4.250 +10.000 +8.500 +7.675 +5.445 (cr)
The command requests the
The analog input module responds with the input values of all channels, in sequence from 0 to 7: +6.000, +7.000,