I/O Modules

6.Only for ADAM-5018: Execute the CJC (cold junction sensor) Calibration command. This can be done with the ADAM utility software. (See the “CJC Calibration” option in the Calibration submenu of the ADAM utility software.)

Figure 4-17: Cold junction calibration

* Note:

Zero calibration and span calibration must be com-

 

pleted before CJC calibration. To calibrate CJC, the

 

thermocouple attached to ADAM-5018 and a stan-

 

dard thermometer should be used to measure a

 

standard known temperature, such as the freezing

 

point of pure water. The amount of offset between the

 

ADAM-5018 and the standard thermometer is then

 

used in the ADAM utility to complete CJC calibration.