5080 Counter/

Command Set

Frequency Module

 

 

 

#aaSi

#aaSi

However, if the response is in frequency mode , you'll see one similar to the example below:

>0000098700000006490000000762000000011600(cr)

As all 4 values are concatenated into one numerical string such as above, we can still easily discern the values of 4 channels specifically as:

0000098700,0000064900,0000076200,0000011600

What you see here is actually the input values of all channels returned from slot 2 of the ADAM-5000 system at address 16h and in decimal format. However, it is not the actual frequency.

Each actual frequency can be obtained by dividing the response value by 100. Therefore, taking an example of the value above, the actual frequency should be:

actual frequency = 98700/100 = 987

If the response is:

>0000F1000002000000031000000DD400(cr)

The command requests the module in slot 2 of the ADAM-5000 system at address 16h to return the input values of all channels.

The module response that input values if all channels are hexdecimal:

0000F100,00020000,00031000,000DD400

The actual frequency can be obtained by transfering hexdecimal format to decimal format .Then divide the response value by 100. Therefore, taking an example of the value above, the actual frequency should be:

F100 (hexdecimal)=24100 (decimal)

actual frequency = 24100/100 = 241

6-128

ADAM-5000

Page 250
Image 250