Chapter 4

Calibration voltage (ADAM-5017/5018)

Module

Input Range

Input Range

Span Calibration

 

Code (Hex)

 

Voltage

 

 

 

 

5018

00h

±15 mV

+15 mV

 

 

 

 

 

01h

±50 mV

+50 mV

 

 

 

 

 

02h

±100 mV

+100 mV

 

 

 

 

 

03h

±500 mV

+500 mV

 

 

 

 

 

04h

±1V

+1 V

 

 

 

 

 

05h

±2.5V

+2.5 V

 

 

 

 

 

06h

±20 mA

+20 mA (1)

 

 

 

 

 

0Eh

J thermocouple

+50 mV

 

 

0 to 760 ºC

 

 

 

 

 

 

0Fh

K thermocouple

+50 mV

 

 

0 to 1000 ºC

 

 

 

 

 

 

10h

T thermocouple

+22 mV

 

 

-100 to 400 ºC

 

 

 

 

 

 

11h

E thermocouple

+80 mV

 

 

0 to 1000 ºC

 

 

 

 

 

 

12h

R thermocouple

+22 mV

 

 

500 to 1750 ºC

 

 

 

 

 

 

13h

S thermocouple

+22 mV

 

 

500 to 1750 ºC

 

 

 

 

 

 

14h

B thermocouple

+15 mV

 

 

500 to 1800 ºC

 

 

 

 

 

5017

07h

Not used

 

 

 

 

 

 

08h

±10 V

+10 V

 

 

 

 

 

09h

±5 V

+5 V

 

 

 

 

 

0Ah

±1 V

+1 V

 

 

 

 

 

0Bh

±500 mV

+500 mV

 

 

 

 

 

0Ch

±150 mV

+150 mV

 

 

 

 

 

0Dh

±20 mA

+20 mV (1)

 

 

 

 

Table 4-8: Calibration voltage of ADAM-5017/5018

ADAM-5000

4-21

Page 61
Image 61
Advantech RS-485 user manual Calibration voltage ADAM-5017/5018