5080 Counter/

Command Set

Frequency Module

 

 

 

$aaSiB

$aaSiB

Name Read Configuration.

Description The command requests the Configuration of slot

Syntax $aaSiB(cr)

$ is a delimiter character.

aa(range 00-FF) represents the 2-character hexadecimal address of the ADAM-5000 system you want to interrogate.

Si identifies the desired slot i

B represents the configuration status command

(cr) is the terminating character, carriage return (0Dh).

Response. !aarrff(cr) if the command is valid.

?aa(cr) if an invalid operation was entered.

There is no response if the module detects a syntax error or communication error or if the specified address does not exist.

!delimiter character indicating a valid command is received.

?delimiter character indicating the command is invalid.

aa(range 00-FF) represents the 2-character hexadecimal address of an ADAM-5000 system.

rr=00 represents Bi-direction counter mode. rr=01 represenrs UP/DOWN counter mode. rr=02 represents Frequency mode.

ffindicates which format is

ff=00 represents the engineer format. ff=02 represents the hexdecimal format.

(cr) is the terminating character, carriage return (0Dh).

6-124

ADAM-5000

Page 246
Image 246
Advantech RS-485 user manual 124