6-112 ADAM-5000
Command Set
#aaSiBB(data) #aaSiBB(data)
sent to the digital output module (ADAM-5056) in slot 1
of the ADAM-5000 system at address 14h. Channels 2,
4, 5, 9 and 12 will be set to ON, and all other channels are
set to OFF.
command: #15S0003A(cr)
response: >(cr)
An output byte with value 3Ah (00111011) is sent to the
digital output module (ADAM-5060) in slot 0 of the
ADAM-5000 system at address 15h. Channels 0, 1, 3, 4
and 5 will be set to ON while channel 2 is set to OFF.
Bits 6 and 7 are not used and always default to 0.
Note: If any channel of the digital output module is config-
ured as the output for an analog input alarm, it
cannot be reconfigured via digital output commands.
Channels used for analog input alarms always have a
higher priority.
5050/5051/5052/5056/
5060/5068 Digital I/O