Chapter 6

 

 

#aaSi

#aaSi

Name

All Analog Data In

Description

Returns the input value of all channels for a specified

 

analog input module of a specified system in engineer-

 

ing units or two’s complement data format

Syntax

#aaSi

 

# is a delimiter character.

 

aa (range 00-FF) represents the 2-character hexadecimal

 

address of the ADAM-5000 system you want to

 

interrogate.

 

Si identifies the I/O slot (i:0 to 3) of ADAM-5000 system

 

you want to read.

 

(cr) is the terminating character, carriage return (0Dh).

Response

!(data)(data)(data)(data) (data)(data)(data)(data)(cr) if the

 

command is valid. (Engineering Unit Data Format)

 

!(dddd)(dddd)(dddd)(dddd)(dddd)(dddd)(dddd)(dddd)(cr)if

 

the command is valid. (Two’s Complement Data Format)

 

?aa(cr) if an invalid operation was entered.

 

There is no response if the module detects a syntax error

 

or communication error or if the specified address does

 

not exist.

 

! delimiter character indicating a valid command was

 

received.

 

? delimiter character indicating the command was

 

invalid.

 

(data) is the input value in engineering units of the

 

interrogated module of the specified system. The (data)

 

from all channels is shown in sequence from 7 to 0. If

 

(data)=” “, it means the channel is invalid.

 

(dddd) is the input value in two’s complement format of

ADAM-5000

6-67

Page 189
Image 189
Advantech RS-485 Syntax #aaSi, Response Datadatadatadata datadatadatadatacr if, Ddddddddddddddddddddddddddddddddcrif