| 5050/5051/5052/5056/ |
Command Set | 5060/5068 Digital I/O |
|
|
#aaSiBB(data) | #aaSiBB(data) |
Name | Digital Data Out |
Description | This command either sets a single digital output channel |
| or sets all digital output channels simultaneously. |
Syntax | #aaSiBB(data)(cr) |
| # is a delimiter character. |
| aa (range |
| address of the |
| Si identifies the slot i (i:0 to 3) of the |
| system which contains the module whose output values |
| you want to set. |
| BB is used to indicate which channel(s) either single or |
| all will be set. |
| Writing to all channels (write a byte): both characters |
| should be equal to zero (BB=00). |
| Writing to a single channel (write a bit): first character is |
| 1, second character indicates channel number which can |
| range from 0h to Fh. The |
| 0h to Fh, and the |
| 7h). |
| (data) is the hexadecimal representation of the digital |
| output value(s). |
| When writing to a single channel (bit) the first character |
| is always 0. The value of the second character is either 0 |
| or 1. |
| When writing to all channels (byte) 2 or |
| are significant. The digital equivalent of these |
| hexadecimal characters represent the channels' values. |
| Note that the number of channels on the |
| and |