| 5080 Counter/ |
Command Set | Frequency Module | |
| ||
|
|
|
#aaSi |
| #aaSi |
Name | Read All Channel Counter (Frequency) Data | |
Description | Return the input value of all channels for the specified | |
| input module for a specified system in engineering unit | |
| only. |
|
Syntax | #aaSi(cr) |
|
| # is a delimiter character. | |
| aa (range | |
| address of the | |
| interrogate. |
|
| Si is the I/O slot of | |
| read. |
|
| (cr) is the terminating character, carriage return (0Dh) | |
Response | >(data) (data) (data) (data) (cr) if the command is valid. | |
| ?aa(cr) if an invalid operation was entered. | |
There is no response if the module detects a syntax error or communication error or if the specified address does not exists.
> is a delimiter character.
? is a delimiter character indicating the command being invalid.
(data) is the input value in engineering units of the interrogated module of the specified system. If the numbers of (data) are ten ,counter/frequency mode is in decimal format.If the numbers of (data) are eight,counter/frequency mode is in hexdecimal format. If (data) = “ ”, it means the channel is invalid.
(cr) is the terminating character, carriage return (0Dh).