Command Set

CPU

 

 

%aannccff

%aannccff

(cr) is the terminating character, carriage return (0Dh).

Example command: %23000A40(cr)

response: !23(cr)

The ADAM-5000 system with address 23h is configured to a baud rate of 115.2 Kbps and with checksum genera- tion or validation.

The response indicates that the command was received.

Wait 7 seconds to let the new configuration setting take effect before issuing a new command to the system.

Note: All configuration parameters can be changed dynami- cally, except checksum and baud rate parameters. They can only be altered when the INIT* terminal is grounded.

Baud Rate

Baud Rate

Code

 

 

 

03h

1200 bps

 

 

04h

2400 bps

 

 

05h

4800 bps

 

 

06h

9600 bps

 

 

07h

19.2 Kbps

 

 

08h

38.4 Kbps

 

 

09h

57.6 Kbps

 

 

0Ah

115.2 Kbps

 

 

Figure 6-1 Baud rate codes

6-6

ADAM-5000

Page 128
Image 128
Advantech RS-485 user manual Example command %23000A40cr, Baud rate codes