5013/5017/5017H/5018

Command Set

Analog Input Alarm

 

 

$aaSiCjAhU(data)

$aaSiCjAhU(data)

Name

Set Alarm Limit

Description

Sets the High/Low alarm limit value for the specified

 

input channel of a specified ADAM-5000 system.

Syntax

$aaSiCjAhU(data)(cr)

 

$ is a delimiter character.

 

aa (range 00-FF) represents the 2-character hexadecimal

 

address of an ADAM-5000 system.

 

SiCj identifies the desired slot i (i : 0 to 3) and the

 

desired analog input channel j (j : 0 to 7).

 

AhU is the Set Alarm Limit command.

 

h indicates alarm type and can have the value H = High

 

alarm, L = Low alarm

 

(data) represents the desired alarm limit setting. The

 

format is always in engineering units.

 

(cr) represents terminating character, carriage return

 

(0Dh)

Response

!aa(cr) if the command was valid

 

There is no response if the system detects a syntax error

 

or communication error or if the specified address does

 

not exist.

 

! delimiter character indicating a valid command was

 

received.

 

aa represents the 2-character hexadecimal address of the

 

corresponding ADAM-5000 system.

 

(cr) represents terminating character, carriage return

 

(0Dh)