I/O Modules

Note: If the above procedure is ineffective, the user must first issue an RTD Self Calibration command $aaSi2 to the module and then complete steps 4 and 5 after self calibration is complete.

Calibration resistances (ADAM-5013)

Input Range

Input Range

Span

Zero

Code (Hex)

 

Calibration

Calibration

 

 

Resistance

Resistance

 

 

 

 

20

Pt, -100 to 100° C

140 Ohms

60 Ohms

 

A = 0.00385

 

 

 

 

 

 

21

Pt, 0 to 100° C

140 Ohms

60 Ohms

 

A = 0.00385

 

 

 

 

 

 

22

Pt, 0 to 200° C

200 Ohms

60 Ohms

 

A = 0.00385

 

 

 

 

 

 

23

Pt, 0 to 600° C

440 Ohms

60 Ohms

 

A = 0.00385

 

 

 

 

 

 

24

Pt, -100 to 100° C

140 Ohms

60 Ohms

 

A = 0.00392

 

 

 

 

 

 

25

Pt, 0 to 100° C

140 Ohms

60 Ohms

 

A = 0.00392

 

 

 

 

 

 

26

Pt, 0 to 200° C

200 Ohms

60 Ohms

 

A = 0.00392

 

 

 

 

 

 

27

Pt, 0 to 600° C

440 Ohms

60 Ohms

 

A = 0.00392

 

 

 

 

 

 

28

Ni, -80 to 100° C

200 Ohms

60 Ohms

 

 

 

 

29

Ni, 0 to 100° C

200 Ohms

60 Ohms

 

 

 

 

Table 4-2: Calibration resistances of ADAM-5013

4-6

ADAM-5000

Page 46
Image 46
Advantech RS-485 user manual Calibration resistances ADAM-5013