6-56 ADAM-5000
Command Set
$aaSi9shhhh $aaSi9shhhh
Example command: $07S29+0042(cr)
response: !07(cr)
The command increases the CJC offset value of the
analog input module in slot 2 of the system at address
07h with 66 counts (42 hex) which equals about 0.6°C.
Note: An analog input module requires a maximum of 2
seconds to perform auto calibration and ranging after
it receives a CJC Calibration command. During this
interval, the module cannot be addressed to perform
any other actions.
5017/5018 Analog Input