Advantech RS-485 user manual Syntax $aaSiAFFff

Models: RS-485

1 348
Download 348 pages 43.54 Kb
Page 185
Image 185

 

 

Chapter 6

 

 

$aaSiAFFff

$aaSiAFFff

Name

 

Set Data Format

Description

 

Sets the data format in engineering units or in two's

 

 

complement format for a specified analog input module

 

 

in a specified system.

Syntax

 

$aaSiAFFff

 

 

$ is a delimiter character.

 

 

aa (range 00-FF) represents the 2-character hexadecimal

 

 

address of the ADAM-5000 system you want to

 

 

configure.

 

 

Si identifies the I/O slot of the ADAM-5000 system

 

 

containing the ADAM-5017H module you want to

 

 

configure.

 

 

AFF represents the set data format command.

 

 

ff represents the 2-character hexadecimal code of the

 

 

data format. 00 is for engineering unit format. 02 is for

 

 

two’s complement format.

Note:

Each channel in an ADAM-5017H module may be set

 

to a different range, but the data formats of all

 

channels in this module must be the same.

 

 

(cr) is the terminating character, carriage return (0Dh).

Response

 

!aa(cr) if the command is valid.

 

 

?aa(cr) if an invalid operation was entered.

There is no response if the module detects a syntax error or communication error or if the specified address does not exist.

! delimiter character indicating a valid command was received.

? delimiter character indicating the command was

ADAM-5000

6-63

Page 185
Image 185
Advantech RS-485 user manual Syntax $aaSiAFFff