Chapter 7

Error Code

Error Type

 

 

00h

OK

 

 

01h

AI module span calibration error

 

 

02h

AI module self-calibration error

 

 

04h

AI module zero calibration error

 

 

08h

AI module data reading error

 

 

10h

CJC reading error

 

 

20h

EEPROM read/write error of

 

AI/AO modules

 

 

7.3System Indicators

While the ADAM-5000 system is in operation the indicators on the front can help you diagnose problems with the system. The table below gives a quick reference of potential problems associated with each status indicator.

Indicator Status

Potential Problems

 

 

 

PWR (Off)

1.

System voltage incorrect

 

2.

Power supply is faulty

 

3.

Other components such as I/O

 

 

modules have power supply shorts

 

 

RUN (Off)

CPU board is faulty

 

 

TX (Off)

Data not sent to adjacent node

 

 

RX (Off)

Data not received from adjacent node

 

 

 

PWR Indicator

In general there are 3 reasons for the system power status LED (PWR) to be OFF.

ADAM-5000

7-3

Page 287
Image 287
Advantech RS-485 user manual System Indicators, PWR Indicator