Command Set | 5017/5018 Analog Input | |
|
|
|
$aaSiER |
| $aaSiER |
Name | Initialize EEPROM data | |
Description | Initializes all EEPROM data in a specified analog input | |
| module to their default values. This command is sent | |
| following a failed attempt to calibrate a module (the | |
| module shows no effect from an attempted calibration). | |
| Following initialization, the problem module should | |
| readily accept calibration. | |
Syntax | $aaSiER(cr) |
|
| $ is a delimiter character. | |
| aa (range | |
| address of the | |
| Si identifies the I/O slot for which you wish to initialize | |
| all EEPROM data. | |
| ER is Initialize all EEPROM data command. | |
| (cr) is the terminating character, carriage return (0Dh) | |
Response | !aa(cr) if the command is valid. | |
| ?aa(cr) if an invalid operation was entered. | |
There is no response if the module detects a syntax error or communication error or if the specified address does not exist.
! delimiter character indicating a valid command was received.
? delimiter character indicating the command was invalid.
aa (range
(cr) is the terminating character, carriage return (0Dh)