| Chapter 6 |
|
| |
$aaSiCj3hh | $aaSiCj3hh | |
Name | Trim Calibration |
|
Description | Trims the specified channel a specified number of units | |
| up or down |
|
Syntax | $aaSiCj3hh(cr) |
|
| $ is a delimiter character. |
|
| aa (range | |
| address of the |
|
| SiCj identifies the I/O slot i (i : 0 to 3) and the channel | |
| j (j : 0 to 3) of the module you want to calibrate. | |
| 3 is the trim calibration command. |
|
| hh is the | |
| value that represents the number of counts by which to | |
| increase or decrease the output current. Each count | |
| equals approximately 1.5µA. Values range from 00 to 5F | |
| and from A1 to FF (hexadecimal), where 00 represents 0 | |
| counts, 5F represents +95 counts, A1 represents | |
| counts and FF represents | |
| decrease and positive numbers increase the output | |
| current according to the number of counts. | |
| (cr) is the terminating character, carriage return (0Dh) | |
Response | !aa(cr) if the command is valid. |
|
| There is no response if the module detects a syntax error | |
| or communication error or if the specified address does | |
| not exist. |
|
! delimiter character indicating a valid command was received.
aa (range