Chapter 6

 

 

@aaSiCjG

@aaSiCjG

Name

Read Initial Counter

 

Description

Read initial counter value of specified module.

Syntax

@aaSiCjG(cr)

 

 

@ is a delimiter character.

 

 

aa (range 00-FF) represents the 2-character hexadecimal

 

address of the ADAM-5000 system.

 

 

SiCj identifies the I/O slot i and the channel j for the

 

module you want to return a prior value.

 

 

G is the last value readback command.

 

 

(cr) is the terminating character, carriage return (0Dh)

Response

!aa(data)(cr) if the command is valid.

 

 

?aa(cr) if an invalid operation was entered.

There is no response if the module detects a syntax error or communication error or if the specified address does not exist.

! delimiter character indicating a valid command was received.

? delimiter character indicating the command was invalid.

aa (range 00-FF) represents the 2-character hexadecimal address of an ADAM-5000 system.

(data) is initial value from 0 to 4294967295.Be aware that (data) has 10 characters.

(cr) is the terminating character, carriage return (0Dh)

ADAM-5000