| 5080 Counter/ |
Command Set | Frequency Module | |
| ||
|
|
|
$aaSiArrff |
| $aaSiArrff |
Name | Set Configuration |
|
Description | Set slot index and counter mode. | |
Syntax | $aaSiArrff(cr) |
|
| $ is a delimiter character. | |
| aa (range | |
| address of the | |
| configure. |
|
| Si identifies the I/O slot i you want to configure. | |
| A is command for setting I/O module configuration. | |
| rr indicates which mode is. | |
| rr=00 represents | |
| rr=01 represenrs UP/DOWN counter mode. | |
| rr=02 represents Frequency mode. | |
| ff indicates which format is | |
| ff=00 represents the engineer format. | |
| ff=02 represents the hexdecimal format. | |
Response | !aa(cr) if the command is valid. | |
| ?aa(cr) if an invalid operation was entered. | |
There is no response if the module detects a syntax error or communication error or if the specified address does not exists.
! delimiter character indicating a valid command was received.
? delimiter character indicating the command was invalid.
aa (range
(cr) is the terminating character, carriage return (0Dh)