I/O Modules

Main Units Supporting Digital Output Holding Function

The Digital Output Holding Function is applicable only to ADAM- 5510 and ADAM-5511. Other main units, such as ADAM-5000/485, ADAM-5000/CAN and ADAM-5000E, do not support this function, since their firmwares will automatically clear the digital output.

Although the firmware of ADAM-5510 and ADAM-5511 will not automatically clear the digital output value, it is nevertheless left as user's free choice to write a program either to clear the digital output or to set the initial value for the system.

The digital output behaviors during power-on and reset are summa- rized in the following table:

ADAM-5056D Digital Output during Power-on and Reset

 

Power-on

Reset

 

 

 

ADAM-5000/485

DO. clear

DO. clear

 

 

 

ADAM-5000/CAN

DO. clear

DO. clear

 

 

 

ADAM-5000E

DO. clear

DO. clear

 

 

 

ADAM-5510

DO. clear

DO. hold

 

 

 

ADAM-5511

DO. clear

DO. hold

 

 

 

Table 4-15: Main Units Supporting Digital Output Holding Funciton

4-36

ADAM-5000

Page 76
Image 76
Advantech RS-485 user manual ADAM-5056D Digital Output during Power-on and Reset