Command Set

5013 RTD Input

 

 

 

$aaSi0

 

$aaSi0

Name

RTD Span Calibration

 

Description

Calibrates a specified RTD input module of a specified

 

system to correct for gain errors.

Syntax

$aaSi0(cr)

 

 

$ is a delimiter character.

 

 

aa (range 00-FF) represents the 2-character hexadecimal

 

address of the ADAM-5000 system which contains the

 

RTD module.

 

 

Si identifies the slot i (i:0 to 3) containing the RTD

 

module to be calibrated.

 

 

0 represents the span calibration command.

 

(cr) is the terminating character, carriage return (0Dh).

Response.

!aa(cr) if the command is valid.

 

?aa(cr) if an invalid operation was entered.

There is no response if the module detects a syntax error or communication error or if the specified address does not exist.

> delimiter character indicating a valid command was received.

? delimiter character indicating the command was invalid.

aa (range 00-FF) represents the 2-character hexadecimal address of an ADAM-5000 system.

(cr) is the terminating character, carriage return (0Dh).