| Chapter 6 |
|
| |
$aaSiCjRhC | $aaSiCjRhC | |
Name | Read Alarm Connection |
|
Description | Return the High/Low alarm limit output connection of a | |
| specified input channel in the addressed | |
| system |
|
Syntax | $aaSiCjRhC(cr) |
|
| $ is a delimiter character. |
|
| aa (range | |
| address of an | |
| SiCj identifies the desired slot i and the desired channel j. | |
| RhC is the command for reading Alarm Connection. | |
| h indicates alarm type and can have the value H = High | |
| alarm, L = Low alarm |
|
| (cr) represents terminating character, carriage return (0Dh) | |
Response | !aaSkCn(cr) if the command was valid | |
| There is no response if the system detects a syntax error | |
| or communication error or if the specified address does | |
| not exist. |
|
| ! delimiter character indicating a valid command was | |
| received. |
|
| aa represents the | |
| corresponding | |
| SkCn identifies the desired slot k | and the desired digital |
| output point n (n : 0 to F) to which the input alarm is | |
| connected. If the values of k and n are ‘*’, the analog | |
| input has no connection with a digital output point. | |
| (cr) represents terminating character, carriage return (0Dh) | |