Name

Initialize EEPROM Data

Description

Initializes all EEPROM data in a specified analog input

 

module to their default values. This command is sent

 

following a failed attempt to calibrate a module (the

 

module shows no effect from an attempted calibration).

 

Following initialization, the problem module should

 

readily accept calibration.

Syntax

$aaSiER(cr)

 

$ is a delimiter character.

 

aa (range 00-FF) represents the 2-character hexadecimal

 

address of the ADAM-5000 system.

 

Si identifies the I/O slot in which you wish to initialize all

 

EEPROM data.

 

ER represents the initialize EEPROM data command.

 

(cr) is the terminating character, carriage return (0Dh)

Response

!aa(cr) if the command is valid.

 

?aa(cr) if an invalid operation was entered.

 

There is no response if the module detects a syntax error

 

or communication error or if the specified address does

 

not exist.

 

! delimiter character indicating a valid command was

 

received.

 

? delimiter character indicating the command was

 

invalid.

 

aa (range 00-FF) represents the 2-character hexadecimal

 

address of an ADAM-5000 system.

 

(cr) is the terminating character, carriage return (0Dh)

ADAM-5000

6-29