Chapter 6

$aaSiCjAhCSkCn$aaSiCjAhCSkCn

Example command: $03S0C1ALCS1C0(cr)

response: !03(cr)

Channel 1 of slot 0 in the ADAM-5000 system at address 03h is instructed to connect its Low alarm to the digital output of point 0 of slot 1 in the same ADAM- 5000 system.

The system confirms it has done so accordingly.

ADAM-5000

6-81

Page 203
Image 203
Advantech RS-485 user manual $aaSiCjAhCSkCn$aaSiCjAhCSkCn, Example command $03S0C1ALCS1C0cr